89422418 Crouzet
Технические характеристики: Heating and / or cooling function
2 independent alarms
Load break detection
2 setpoint which can be selected remotely
Manual / automatic power adjustment
RS 485 / MODBUS-JBUS serial communication option, General characteristics
Supply 100 to 240 VAC, 24 VACDC
Frequency (Hz) 50 / 60
Tolerance -15 % +10 % Un
Consumption 8 VA max.
Display measurement red LEDs-4 digits, 7 segment, height 10 mm
Display setpoint green LEDs-4 digits, 7 segment, height 7,5 mm
Control characteristics
Control algorithm PID with auto-tune and adaptive tune : SMART
Control type heat or cool
heat / cool
Sampling time linear input 250 ms
Sampling time TC and RTD input 500 ms
Proportional band Pb heat or cool 1,0 to 100 % of scale amplitude
Proportional band Pb heat - cool 1,5 to 100 % of scale amplitude
Proportional band Pb
Note : if Pb = 0 % discrete action
Hysteresis (during discrete action) 0,1 to 10 % of scale amplitude
Integral time ti
Note : if ti > 20 min
20 s to 20 min
integral action is inactive
Derivative time td.
Note : if td=0
1 s to 10 min
derivative action is inactive
Cycle time heating 1 s →200 s
Cycle time cooling 1 s →200 s
Heat-cool control
Cool proportional band rC x heat proportional band
Heat-cool control
rC : relative gain 0,20 →1,00
Heat-cool control
dead.overlap band -20 % to + 50 % of the heat proportional band
Inputs
Thermocouples J, K, R, S, and N IEC 584-1
Thermocouples L DIN 43710
Reference junction Automatic cold junction compensation : 0 to 50 oC
(Thermocouples)
Reference junction drift 0,1 °C / °C
Input impedance (kΩ) > 1 M Ω
Calibration (IEC 584-1)
Resist. temp. detector 3-wire Pt 100 conforming to DIN
43760
Line resistance 20 Ω max. (Resistance temperature detector)
Input type and standard range TC L (0/400 °C) (0/1650°F) (0/900 °C)
J (0/400 °C) (0/1830°F) (0/1000 °C)
K (0/400 °C) (0/2190°F) (0/1200 °C)
N (0/1400 °C) (0/2550°F)
R (0/1760 °C) (0/3200°F)
S (0/1760 °C) (0/3200°F)
Input types and standard rangeRTD Pt100 (-199,9/400,0 °C) (-199,9/400,0°F)
(-200/800 °C) (-330/1470°F)
Measurement range - 1999 →+ 4000
Decimal point adjustable : - - - -, - - -. -, - -. - -, -. - - -
Current transformer input for monitoring the load break
Inputs 50 mAAC
Measurement range with transformer 10 A →100 A, Resolution 10 to 20 A : 0.1 A
21 to 100 A : 1 A
Measurement logic threshold Relay output : NO or NC
Logic output : level 1 or 0
Measurement update period 50 ms
Setpoints - main setpoint : SP
- auxiliary setpoint : SP2
Selection input
SP/SP2
50 mA AC
selection via external N/C type contact
Output
Type of output discontinuous
Action type can be programmed for heating and/or cooling
Limitation of output power : SOFT-START- heat action adjustable from 0 to 100 %
Limitation of output power : SOFT-START-heat/cool
action adjustable from -100 to +100 %
Output specification
OUT 1 Main output N/O contact 3A 250 V AC resistive (N/C contact is possible via a jumper)
OUT 1 Main output logic Level 0 : <0,5 V DC
Level 1 :
14 V DC±20 % @ 20 mA max
24 V DC±20 % @ 1 mA max
Main output cycle time 1 s →99 s
OUT 2 Cool output or alarm 1 output N/O-2A contact, 250 V AC resistive
OUT 3 Load break output and/or alarm 2 output N/O-2A contact, 250 V AC resistive
Description of alarms 1 and 2
Type of output direct or reverse
Functions absolute alarm
band alarm
deviation alarm
Reset to zero Manual / automatic
Inhibition Configuration
Alarm threshold - absolute alarm absolute value independent from SP
Alarm threshold - band alarm value relative to SP, adjustable from 0 to 500 °C/°F
Alarm threshold - deviation alarm value relative to SP, adjustable from-500 °C/°F (negative deviation) to + 500 °C/°F (positive deviation)
Alarm 0.1 to 10 % of scale amplitude
Serial link
Type RS485
Protocol MODBUS, J.BUS
Address 1 →255
Number of data bits 8
Transmission speed 600 →19 200 Bauds
Parity even, odd, no
Stop bit 1
Physical details and protection
Insulation resistance conforming to IEC 348 > 100 MΩ
Insulation voltage according to IEC 348 1500 V
Immunity to interference conforming to IEC 801-4 Level 3
Immunity to interference conforming to IEC 801-2 8000 V
Accuracy ± 0.2 % of the full measurement scale ± 1 digit at an ambient temperature of 25 oC at Un
Operating temperature range (°C) 0 →+50
Storage temperature range (°C) -20 →+70 °C
Relative humidity (no condensation) 20 →85 % Rh
Housing
Housing material self-extinguishing UL94 grade VO
Front panel Polycarbonate membrane
Protection class according to IEC 529 (IEC 70-1) IP 54
Connection screw terminals
Weight (g) 250
Approvals
UL / CSA in progress
Protection
Safe-guard detects a fault in the equipment caused by external interference and activates automatic reset without modification of the process.
Switch the configuration and calibration are accessed via an internal switch, can only be accessed when the device is unplugged.
Medium air
oil
water
rC relative gain 1,00
0,80
0,40
Cycle time cooling 10 s
4 s
2 s