Технические характеристики: Supply
Supply voltage Un 3 x 208 →3 x 480 V AC *
Voltage supply tolerance -12 % / +10 %
Operating range 183 →528 V AC
AC supply voltage frequency 50 / 60 Hz ±10 %
Galvanic isolation of power supply/measurement No
Power consumption at Un 22 VA in 400 VAC, 50 Hz
Immunity from micro power cuts 10 ms
Inputs and measuring circuit
Measurement ranges 183 →528 V AC
Selection of phase-phase nominal voltage Un 208 - 220 - 380 - 400 - 415 - 440 - 480 V
Frequency of measured signal 50 →60 Hz ± 10 %
Max. measuring cycle time 150 ms/True RMS measurement
Voltage threshold adjustment 2 →20 % of selected Un
(-2 to -12 % across the 3 x 208 V AC range / -2 to -17 % across the 3 x 220 V AC range / 2 to 10 % across the 3 x 480 V AC range)
Voltage threshold hysteresis 2 % of fixed Un
Asymmetry threshold hysteresis 2 % of fixed Un
Asymmetry threshold adjustment 5 to 15 % of selected Un
Display precision ± 3 % of the displayed value
Repetition accuracy with constant parameters ± 0,5 %
Measuring error with voltage drift < 1 % across the whole range
Measuring error with temperature drift < 0,05 %/ °C
Maximum regeneration (phase failure) 70 %
Timing
Delay on thresold crossing 0.1 to 10 s 0 +10 %
Repetition accuracy with constant parameters ± 3 %
Reset time 1500 ms
Delay on pick-up ≤ 650 ms
Alarm on delay time max. < 200 ms
Output
Type of output 1 single pole changeover relay
Type of contacts No cadmium
Maximum breaking voltage 250 V AC/DC
Max. breaking current 5 A AC/DC
Min. breaking current 10 mA / 5 V DC
Electrical life (number of operations) 1 x 105
Breaking capacity (resistive) 1250 VA AC
Maximum rate 360 operations/hour at full load
Operating categories acc. to IEC/EN 60947-5-1 AC 12, AC 13, AC 14, AC 15, DC 12, DC 13, DC 14
Mechanical life (operations) 30 x 106